The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC
Authors
Xiaojun Chen, Wenjie Zheng, Shu Huang, Hui Chen
Corresponding Author
Xiaojun Chen
Available Online September 2015.
- DOI
- 10.2991/ifeesm-15.2015.181How to use a DOI?
- Keywords
- Operating maintenance; Lightning overvoltage; Distribution networks; Overhead line.
- Abstract
The model of lighting direct strokes on 10 kV distribution line in Guangzhou was built and the transient procedure was considered based on the software of PSCAD/ECTDC. The effect of arrest and ground resistance operating maintenance on lightning overvoltage in distribution networks has been discussed. The results show that operating maintenance of arrest has significant suppression on lightning overvoltage. In addition, the ground resistance of tower has little influence on the lightning overvoltage.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Xiaojun Chen AU - Wenjie Zheng AU - Shu Huang AU - Hui Chen PY - 2015/09 DA - 2015/09 TI - The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC BT - Proceedings of the 2015 International Forum on Energy, Environment Science and Materials PB - Atlantis Press SP - 984 EP - 988 SN - 2352-5401 UR - https://doi.org/10.2991/ifeesm-15.2015.181 DO - 10.2991/ifeesm-15.2015.181 ID - Chen2015/09 ER -