A Test System for Hidden Failure Based on Hybrid State Estimation
- DOI
- 10.2991/icmii-15.2015.168How to use a DOI?
- Keywords
- power system management; hidden failure; state estimation; static condition; WAMS
- Abstract
Hidden failures in relay may cause invalidation of protection equipment so that system faults cannot be detected. These faults will lead to cascading outages in severe cases. At present, effective methods lack in monitoring hidden failures. A hybrid state estimation which uses system data collected from both SCADA and WAMS is proposed. The state value obtained from state estimation is regarded as reference value. The measurement value uploaded by protection information system is compared with reference value. If the difference exceeds default threshold value, hidden failure can be proved to exist in relay. A test system for hidden failure is established according to analysis above. This system can be used on the long-term, real-term, and on-line monitoring of relay. Example demonstrates that this system can be used to check the hidden failure in relay effectively.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Zhongqing Li AU - Yuan Tian AU - Chen Liang AU - Yan Hu AU - Xiang Gao PY - 2015/10 DA - 2015/10 TI - A Test System for Hidden Failure Based on Hybrid State Estimation BT - Proceedings of the 3rd International Conference on Mechatronics and Industrial Informatics PB - Atlantis Press SP - 953 EP - 966 SN - 2352-538X UR - https://doi.org/10.2991/icmii-15.2015.168 DO - 10.2991/icmii-15.2015.168 ID - Li2015/10 ER -