Seismic Vulnerability Analysis of the High-end Suspended Converter Valve Hall Circuit in the ±800kV Converter Station
- DOI
- 10.2991/978-94-6463-449-5_82How to use a DOI?
- Keywords
- High-end suspended converter valve hall circuit; Suspended converter valve; Finite element; Seismic vulnerability; Multiple stripe analysis
- Abstract
Suspended converter valve hall circuit is a crucial subsystem within the UHV converter station. It is characterized by electrical equipment possessing attributes of “high, large, heavy, and flexible,” making them prone to seismic-induced damage. In order to evaluate the seismic performance and vulnerability of the equipment within this circuit environment, this study establishes a refined finite element model for the high-end valve hall circuit of a specific 800kV converter station. Through time-history response analysis, the seismic response characteristics and potential failure modes under seismic action are investigated. Utilizing Multiple stripe analysis method, seismic vulnerability curves for each failure mode as well as the overall circuit are obtained. A comparative analysis is conducted between the overall circuit vulnerability curve and the circuit vulnerability curve considering each equipment failure as an independent event. This study serves as a reference for seismic reinforcement of critical equipment in existing converter stations at the circuit level, establishing the groundwork for evaluating the seismic resilience of converter stations. The results indicate that the base frequency of the converter valve tower in the valve hall is relatively low, leading to excessive bottom displacement response under seismic action. Moreover, significant stress responses are observed in the electrical component support structures, post insulators, and 800kV wall bushings within the valve tower layers under seismic action. Failure modes of the high-end valve hall circuit include relative displacement of adjacent converter valve tower bases, exceeding stress limits in electrical component support structures within the layers, as well as exceeding stress limits at the bottom of post insulators and 800kV wall bushings. Furthermore, the failures of each equipment are correlated, and treating equipment failures as independent events would greatly overestimate the vulnerability of the circuit.
- Copyright
- © 2024 The Author(s)
- Open Access
- Open Access This chapter is licensed under the terms of the Creative Commons Attribution-NonCommercial 4.0 International License (http://creativecommons.org/licenses/by-nc/4.0/), which permits any noncommercial use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license and indicate if changes were made.
Cite this article
TY - CONF AU - Jinyu Hu AU - Qiang Xie PY - 2024 DA - 2024/06/30 TI - Seismic Vulnerability Analysis of the High-end Suspended Converter Valve Hall Circuit in the ±800kV Converter Station BT - Proceedings of the 2024 8th International Conference on Civil Architecture and Structural Engineering (ICCASE 2024) PB - Atlantis Press SP - 826 EP - 841 SN - 2589-4943 UR - https://doi.org/10.2991/978-94-6463-449-5_82 DO - 10.2991/978-94-6463-449-5_82 ID - Hu2024 ER -