Research on fault of turn to turn short circuit of rotor winding of large hydro generator
- DOI
- 10.2991/mmebc-16.2016.155How to use a DOI?
- Keywords
- Hydro Generator, Fault of Rotor Winding Inter-turn Short Circuit, Failure Criteria
- Abstract
With the rapid development of hydropower, the fault of roto winding inter-turn short circuit of large hydro generator set is more and more obvious. We did the research of fault mechanism of turn to turn short circuit of rotor winding of hydro generator, and concerned the condition of saturation of the generator. After a series of deductions, we obtain the following criteria, (I_fc-I_f0)/I_f0 > %. In the formula, % general take 1%~2%. In the actual working conditions, using the formula to calculate the normal operation of the excitation current, compared with the actual measured value, if the deviation is large, it can be determined whether the turn to turn short circuit
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Meiqi Song PY - 2016/06 DA - 2016/06 TI - Research on fault of turn to turn short circuit of rotor winding of large hydro generator BT - Proceedings of the 2016 6th International Conference on Machinery, Materials, Environment, Biotechnology and Computer PB - Atlantis Press SP - 732 EP - 735 SN - 2352-5401 UR - https://doi.org/10.2991/mmebc-16.2016.155 DO - 10.2991/mmebc-16.2016.155 ID - Song2016/06 ER -