Electrical Field Analysis and Optimizing of High Voltage Bushing Based on Maxwell
- DOI
- 10.2991/meic-14.2014.63How to use a DOI?
- Keywords
- outlet insulation structure; FEM; electrical-field calculations; Maxwell;optimizing
- Abstract
In this paper, it was mainly discussed the electrical field analysis of the high voltage outlet in the insulation structure, which was a part of the transformers manufacture. Firstly, the electrical field of 500kV transformers-outlet devices inside the enclosure was modeled in Maxwell electrostatics solution type and calculated under the industrial frequency withstands voltage with Finite Element Method. The calculation was used to analyze the intensity of electric field about the oil gaps and that around the equalizing ring surface. Then, a model simplification was made and the shape parameters were defined. Further optimizations from the Maxwell optimetrics department were used to search for the optimal solutions. At last, the solutions were reused in the former model and we could contrast the safety factor of the oil gaps and the intensity of the equalizing ring. The result turned out to be effective to optimize the high voltage outlet in the insulation structure.
- Copyright
- © 2014, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Linsuo Zeng AU - Lei Zhao PY - 2014/11 DA - 2014/11 TI - Electrical Field Analysis and Optimizing of High Voltage Bushing Based on Maxwell BT - Proceedings of the 2014 International Conference on Mechatronics, Electronic, Industrial and Control Engineering PB - Atlantis Press SP - 282 EP - 285 SN - 2352-5401 UR - https://doi.org/10.2991/meic-14.2014.63 DO - 10.2991/meic-14.2014.63 ID - Zeng2014/11 ER -