Failure Analysis on Phase B Adjustable Mechanisms of 220KV Lateral 2801 Switch in Da Yuan Substation
- DOI
- 10.2991/mecae-18.2018.92How to use a DOI?
- Keywords
- Screw, Corrosion fracture, Scanning electron microscope analysis
- Abstract
In this paper, the failure of the switch operation caused by a screw breaking of adjustable mechanisms is analyzed. A number of tests, such as macroscopic examination, chemical composition analysis, metallographic test, scanning electron microscope analysis and hardness test, were carried out on the fracture screw sample. From the perspective of metal analysis, it is verified that the failure of the sample is due to the failure of material, resulting in corrosion fracture in the coastal industrial environment and tensile stress interaction. Put forward the checkpoint, do a good job in metal technical supervision, strengthen the quality acceptance and management of the equipment and its parts in the power grid, then, the chances of a similar accident can be reduced.
- Copyright
- © 2018, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yupeng Xie PY - 2018/03 DA - 2018/03 TI - Failure Analysis on Phase B Adjustable Mechanisms of 220KV Lateral 2801 Switch in Da Yuan Substation BT - Proceedings of the 2018 International Conference on Mechanical, Electronic, Control and Automation Engineering (MECAE 2018) PB - Atlantis Press SP - 511 EP - 515 SN - 2352-5401 UR - https://doi.org/10.2991/mecae-18.2018.92 DO - 10.2991/mecae-18.2018.92 ID - Xie2018/03 ER -