Research on Availability of Data Center UPS Power Supply System
- DOI
- 10.2991/jimec-18.2018.63How to use a DOI?
- Keywords
- data center, ups, power system, redundancy, availability, energy saving
- Abstract
According to the requirements of national standard for data center infrastructure, the typical case study is used to analyze the architecture, advantages and disadvantages of the UPS dual-bus 2N redundant power supply system widely used in large and medium-sized data centers and establish the power supply system availability model to calculate its availability in this paper, so as to analyze the factors affecting the reliability of the data center and the development history of the data center power supply system, and verify the availability of the revised National standard A-level data center "One way (N+1) UPS and one way mains" double bus redundant power supply in GB50174-2017 data center design specification, and analyze its advantages in usability and energy efficiency, investment, and application development prospects.
- Copyright
- © 2019, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Chai Yongcai AU - Li Changchun AU - Li Qun AU - Yao Jianqiang PY - 2018/12 DA - 2018/12 TI - Research on Availability of Data Center UPS Power Supply System BT - Proceedings of the 2018 3rd Joint International Information Technology,Mechanical and Electronic Engineering Conference (JIMEC 2018) PB - Atlantis Press SP - 298 EP - 302 SN - 2589-4943 UR - https://doi.org/10.2991/jimec-18.2018.63 DO - 10.2991/jimec-18.2018.63 ID - Yongcai2018/12 ER -