A New Distance Relaying Algorithm for Series Compensated Transmission Lines Based on Micro-Processor
Authors
Yuchao Qiao, Zhenyu Xu, Jiangwen Meng, Shupeng Li
Corresponding Author
Yuchao Qiao
Available Online October 2015.
- DOI
- 10.2991/iwmecs-15.2015.156How to use a DOI?
- Keywords
- Distance relaying algorithm, series compensated transmission lines, fault impedance, fault transient process.
- Abstract
A new and simple distance relaying algorithm based on KVL for series compensated transmission lines is discussed in this paper. The fault impedance can be calculated accurately by solving the 3-order fault loop equations consisting of fault phase voltage, current, the differential and integral of current. In theory, it studies the applicability of the scheme in fault transient process, and put forward the corresponding solution. The simulation test shows that the proposed algorithm operates better than the traditional scheme for the series compensated transmission lines.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yuchao Qiao AU - Zhenyu Xu AU - Jiangwen Meng AU - Shupeng Li PY - 2015/10 DA - 2015/10 TI - A New Distance Relaying Algorithm for Series Compensated Transmission Lines Based on Micro-Processor BT - Proceedings of the 2015 2nd International Workshop on Materials Engineering and Computer Sciences PB - Atlantis Press SP - 786 EP - 792 SN - 2352-538X UR - https://doi.org/10.2991/iwmecs-15.2015.156 DO - 10.2991/iwmecs-15.2015.156 ID - Qiao2015/10 ER -