Analysis and Assessment on Distribution Voltage Sag Based on Stepped Current Protection
- DOI
- 10.2991/itms-15.2015.73How to use a DOI?
- Keywords
- Voltage sag; duration; stepped current protection; protection zone; Assessment
- Abstract
The duration of voltage sag caused by fault is depended on the fault clearing time of the protection system. In traditional assessments on voltage sag are simply assumed that the duration obeys some distribution of random or is a constant value. In order to depict the duration of voltage sags more precisely, time characteristic of stepped current protection and protection scope of instantaneous current protection are taken into consideration, the two demarcation points of the protection operation on line are determined, the protection operation time of every segment is analyzed. An example is simulated by PSCAD/EMTDC software, and it is shown that more reasonable assessment is obtained by precise duration of voltage sag.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Li Ma PY - 2015/11 DA - 2015/11 TI - Analysis and Assessment on Distribution Voltage Sag Based on Stepped Current Protection BT - Proceedings of the 2015 International Conference on Industrial Technology and Management Science PB - Atlantis Press SP - 307 EP - 310 SN - 2352-538X UR - https://doi.org/10.2991/itms-15.2015.73 DO - 10.2991/itms-15.2015.73 ID - Ma2015/11 ER -