Coordinated Restraining of SSO via SSDC and SEDC in hybrid AC-DC System Containing MMC-HVDC
- DOI
- 10.2991/ipemec-15.2015.86How to use a DOI?
- Keywords
- MMC-HVDC; sub-synchronous oscillation; SSDC; SEDC; coordinated control strategy
- Abstract
In this paper, aiming on the sub-synchronous oscillation (SSO) of hybrid AC-DC transmission system which contains modular multilevel converter based High Voltage Direct Current (MMC-HVDC), the coordinated control of sub-synchronous oscillation damping controller (SSDC) and supplementary excitation damping controller (SEDC) is researched. Firstly, aiming on the hybrid system, the structure and parameters of SSDC and SEDC are designed. Then, the practicability of the coordinated control of SSO via SSDC and SEDC is studied in both theory an electrical damping characteristics. Finally, the simulation model with 335 levels is built on PSCAD/EMTDC, and the results validate the correctness of the conclusion and the efficiency of the coordinated control strategy. It is found that SSDC and SEDC can superpose each other on increasing the electrical damping characteristic of whole system, and the coordinated control strategy proposed in this paper is practicabe.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Shupeng Li AU - Zhenyu Xu AU - Yuchao Qiao PY - 2015/05 DA - 2015/05 TI - Coordinated Restraining of SSO via SSDC and SEDC in hybrid AC-DC System Containing MMC-HVDC BT - Proceedings of the 2015 International Power, Electronics and Materials Engineering Conference PB - Atlantis Press SP - 453 EP - 458 SN - 2352-5401 UR - https://doi.org/10.2991/ipemec-15.2015.86 DO - 10.2991/ipemec-15.2015.86 ID - Li2015/05 ER -