Improvement of Chromatographic Detection Unit
- DOI
- 10.2991/ifeesm-17.2018.398How to use a DOI?
- Keywords
- Dissolved gas analysis; on-line monitoring; double-column-double detector module; linear response.
- Abstract
The separation and detection modules of the chromatographic system for the transformer gas-in-oil on-line monitoring is improved. The former single-column separation detection module is improved to double-column separation detection module, and compared with single-column detection module. The results show that the double-column detection module has a better separation performance and the separation process could be completed within 13min. The new detector has a linear response for all the fault gases in the whole detection range, which greatly reducing the workload and calibration time. The system exhibited good stability and high accuracy. The deviation of repeated test is less than 5%, and the deviation from off-line measurement is less than 15%.
- Copyright
- © 2018, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Gang-Qiang Xia AU - Gao-Ming Wang PY - 2018/02 DA - 2018/02 TI - Improvement of Chromatographic Detection Unit BT - Proceedings of the 2017 3rd International Forum on Energy, Environment Science and Materials (IFEESM 2017) PB - Atlantis Press SP - 2200 EP - 2205 SN - 2352-5401 UR - https://doi.org/10.2991/ifeesm-17.2018.398 DO - 10.2991/ifeesm-17.2018.398 ID - Xia2018/02 ER -