Improving the Reactive Power Compensation Strategy of UPQC
- DOI
- 10.2991/ifeesd-16.2016.172How to use a DOI?
- Keywords
- decoupling control; coordinated control; reactive power; UPQC
- Abstract
This paper describes a reactive power control strategy based on the unified power quality conditioner (UPQC). The shunt unit is mainly used to compensate the reactive power based on the active and reactive power decoupling control. Because the series inverter is usually in the bypass switch state, the power coordinated control strategy is also presented. Using series/shunt unit together to compensate reactive power, we can reduce the capacity of shunt inverter. The simulation proved that the control method not only can compensate the active power on the premise of ensuring the system stability, but also can guarantee the stability of the load voltage.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Tongshuo Zhang AU - Lixin Wu AU - Libo Han PY - 2016/05 DA - 2016/05 TI - Improving the Reactive Power Compensation Strategy of UPQC BT - Proceedings of the 2016 International Forum on Energy, Environment and Sustainable Development PB - Atlantis Press SP - 965 EP - 970 SN - 2352-5401 UR - https://doi.org/10.2991/ifeesd-16.2016.172 DO - 10.2991/ifeesd-16.2016.172 ID - Zhang2016/05 ER -