Proceedings of the 2015 2nd International Forum on Electrical Engineering and Automation (IFEEA 2015)

Effect of Shed Configuration on AC Flashover Performance of Polluted Porcelain Insulators

Authors
Yawei Li, Xinghai Zhang, Xiaolei Yang, Huan Bai, Lei Sun
Corresponding Author
Yawei Li
Available Online January 2016.
DOI
10.2991/ifeea-15.2016.3How to use a DOI?
Keywords
Shed configuration, Porcelain insulator, pollution flashover, AC
Abstract

The flashover of polluted insulator is one of the serious problems which should be taken into account in the design and coordination of high voltage insulation. In order to clarify the influence of umbrella shape configurations on the pollution flashover characteristics of AC suspension porcelain insulators, pollution flashover tests have been operated for 11 types of insulators with different umbrella shape configurations. The results indicate that the specific leakage distance increase with the enlargement of diameter and height of insulators, and the increasing severities are relevant to their umbrella shapes. The specific leakage distance of normal type insulators increase more significantly than that of outer-rib insulators with geometrical dimensions enlarging. With equal diameter or height, the specific leakage distance of normal type insulator is bigger than that of outer-rib insulator. And the leakage distance availabilities of normal insulators are superior to that of outer-rib insulator with the same geometrical dimensions. The test results also demonstrate that the contaminated flashover performances of insulators with bigger geometrical dimensions are better than that with smaller geometrical dimensions with the same umbrella shape, this is because that the bigger the geometrical dimensions, the longer the leakage length, and the contamination flashover voltage of certain pollution level is determined by both the umbrella shape configuration and the leakage length of insulator.

Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Download article (PDF)

Volume Title
Proceedings of the 2015 2nd International Forum on Electrical Engineering and Automation (IFEEA 2015)
Series
Advances in Engineering Research
Publication Date
January 2016
ISBN
978-94-6252-153-7
ISSN
2352-5401
DOI
10.2991/ifeea-15.2016.3How to use a DOI?
Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Cite this article

TY  - CONF
AU  - Yawei Li
AU  - Xinghai Zhang
AU  - Xiaolei Yang
AU  - Huan Bai
AU  - Lei Sun
PY  - 2016/01
DA  - 2016/01
TI  - Effect of Shed Configuration on AC Flashover Performance of Polluted Porcelain Insulators
BT  - Proceedings of the 2015 2nd International Forum on Electrical Engineering and Automation (IFEEA 2015)
PB  - Atlantis Press
SP  - 11
EP  - 17
SN  - 2352-5401
UR  - https://doi.org/10.2991/ifeea-15.2016.3
DO  - 10.2991/ifeea-15.2016.3
ID  - Li2016/01
ER  -