Research on Design Schemes of 500kV Convertor Station Grounding Grid
Authors
Wei Chen, Yong Sun, Zihan Chen, Tong Wang, Youping Fan
Corresponding Author
Wei Chen
Available Online December 2016.
- DOI
- 10.2991/icsma-16.2016.86How to use a DOI?
- Keywords
- convertor station; design; grounding grid; grounding resistance; Soil resistivity
- Abstract
With the development of HVDC, transmission capacity and transmission voltage level are both increasing. Under this situation, designing reliable grounding grid is more demanding. For areas with high soil resistivity, the grounding parameters can hardly meet relevant requirements. To solve this problem, this paper takes Luxi convertor station as an example to illustrate the designing process, and analyzes different design schemes. The results show that for areas with high deep soil resistivity the effect of using vertical grounding rods is slight, while the one of lengthening horizontal grounding objects is evident.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Wei Chen AU - Yong Sun AU - Zihan Chen AU - Tong Wang AU - Youping Fan PY - 2016/12 DA - 2016/12 TI - Research on Design Schemes of 500kV Convertor Station Grounding Grid BT - Proceedings of the 2016 4th International Conference on Sensors, Mechatronics and Automation (ICSMA 2016) PB - Atlantis Press SP - 489 EP - 496 SN - 1951-6851 UR - https://doi.org/10.2991/icsma-16.2016.86 DO - 10.2991/icsma-16.2016.86 ID - Chen2016/12 ER -