The Electrical Breakdown of PVC and PMMA Barrier in Oil Insulator under Non-Uniform Field
- DOI
- 10.2991/icmmse-16.2016.25How to use a DOI?
- Keywords
- Electrical breakdown, Non-uniform field, PVC, PMMA, Solid insulator
- Abstract
This paper presents breakdown test of Polyvinyl chloride hard (PVC), Polymethyl methacrylate (PMMA) under non-uniform electric field in transformer oil. PVC and PMMA are placed between point-plate electrodes. The result of the experiment shows that the breakdown voltage of point-plate electrodes is lower than point-point electrodes. PVC endures more breakdown voltage than PMMA. The breakdown voltage of transformer oil with double barriers placed close to electrode is maximum value at 216.5 kV and it is higher than that for single barrier of 205 kV. The results of the experiment can be used to design the blockage room between the conductor and ground in the transformer oil which has the limit space and can endure high breakdown voltage, and it suits the non-uniform electric field characteristics as well.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Tonmitr Kittipong AU - Kaewrawang Arkom PY - 2016/03 DA - 2016/03 TI - The Electrical Breakdown of PVC and PMMA Barrier in Oil Insulator under Non-Uniform Field BT - Proceedings of the 2016 International Conference on Mechanics, Materials and Structural Engineering PB - Atlantis Press SP - 143 EP - 147 SN - 2352-5401 UR - https://doi.org/10.2991/icmmse-16.2016.25 DO - 10.2991/icmmse-16.2016.25 ID - Kittipong2016/03 ER -