Research on the SF6 decomposition components of the GIS bus spike PD and the insulator surface PD
- DOI
- 10.2991/icmmita-15.2015.186How to use a DOI?
- Keywords
- SF6; bus spike; partial discharge; ratio of components
- Abstract
According to the problem that the intelligence is not high of the recognition of GIS PD types by SF6 decomposition components, using the real 110kV GIS platform, simulating two kinds of insulation defects PD of SF6 gas, and making the research on the change of the four kinds of gases of CO2?CF4?SO2F2,and SOF2,then making the research on the ratio of components of c(SOF2)/c(SO2F2), and c(CF4+CO2)/c(SOF2+SO2F2). The results show that the two types of ratio of components of the GIS bus spike PD and the insulator surface PD are significantly different. Therefore, the two types of ratio of components can as the features to identify the GIS bus spike PD and the insulator surface PD.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Shen Du AU - Jiangjiang Qu PY - 2015/11 DA - 2015/11 TI - Research on the SF6 decomposition components of the GIS bus spike PD and the insulator surface PD BT - Proceedings of the 2015 3rd International Conference on Machinery, Materials and Information Technology Applications PB - Atlantis Press SP - 1010 EP - 1013 SN - 2352-538X UR - https://doi.org/10.2991/icmmita-15.2015.186 DO - 10.2991/icmmita-15.2015.186 ID - Du2015/11 ER -