Analysis of A 220kV Current Transformer Explosion Accident
- DOI
- 10.2991/icmmct-16.2016.288How to use a DOI?
- Keywords
- current transformer; fault analysis; power quality; harmonic voltage; flicker
- Abstract
In this paper, the explosion accident of a 220kV current transformer in a 220kV substation is studied. It uses method of scene investigation and test to analyses the accident based on the principle and characteristics of current transformer. Through the analysis, this paper holds that reducing in main insulation electrical strength caused by Long-term high harmonic voltage and main insulation breakdown caused by flicker impact are main causes of the accident. And it also proposes a variety of management methods and technical measures to avoid this kind of accident. This paper provides a reference for the analysis of the same type of accident.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yi Zhu AU - Hua Rong AU - Xu Liu AU - Honggang Ren AU - Shimin Wang AU - Aimin Wang AU - Hai Wang AU - Jia Wang PY - 2016/03 DA - 2016/03 TI - Analysis of A 220kV Current Transformer Explosion Accident BT - Proceedings of the 2016 4th International Conference on Machinery, Materials and Computing Technology PB - Atlantis Press SP - 1450 EP - 1454 SN - 2352-5401 UR - https://doi.org/10.2991/icmmct-16.2016.288 DO - 10.2991/icmmct-16.2016.288 ID - Zhu2016/03 ER -