Research on Capacitor Bank Failure Processing Methods
Authors
Rui Tong, Jiyong Liu, Ning Wang, Ruiguo Chen, Qinghao Wang, Yanjun Pang, Bo Zhang, Hainan Su, Yue Yang, Enlu Wang, Wenguang Zhang
Corresponding Author
Rui Tong
Available Online March 2016.
- DOI
- 10.2991/icmmct-16.2016.274How to use a DOI?
- Keywords
- tapped; discharge coil; unbalanced voltage; voltage ratio
- Abstract
Aiming to the problem of running with the capacitor bank balance protection action causing tripping, by on-site analysis of the phenomenon and the capacitor discharge coil voltage ratio test checks, secondary coil voltage has relatively large errors caused by the tapped discharge coil. When the system voltage fluctuations, voltage unbalance will break through the setting value, causing balance protection action conclusions; proposed discharge coil tapped in the transfer test or tuning capacitor bank balance protection action value, the voltage ratio between whole primary and secondary should be checked of the discharge coil.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Rui Tong AU - Jiyong Liu AU - Ning Wang AU - Ruiguo Chen AU - Qinghao Wang AU - Yanjun Pang AU - Bo Zhang AU - Hainan Su AU - Yue Yang AU - Enlu Wang AU - Wenguang Zhang PY - 2016/03 DA - 2016/03 TI - Research on Capacitor Bank Failure Processing Methods BT - Proceedings of the 2016 4th International Conference on Machinery, Materials and Computing Technology PB - Atlantis Press SP - 1391 EP - 1394 SN - 2352-5401 UR - https://doi.org/10.2991/icmmct-16.2016.274 DO - 10.2991/icmmct-16.2016.274 ID - Tong2016/03 ER -