Research on Unbalance Phase Current of 500kV AC Transmission Line in Yibin UHV Converter Station
Authors
M. Tang, C. Zhang, M. Li, L.J. Ding, H. Zhang, W. Wei, F. Tang
Corresponding Author
M. Tang
Available Online October 2015.
- DOI
- 10.2991/icitmi-15.2015.34How to use a DOI?
- Keywords
- Parallel transmission line; Unbalanced Current; Inductor Model
- Abstract
Unbalance phase current appeared in the 500kV overhead transmission line during the system commission of ± 800kV Binjin UHV DC transmission project. An inductor model of parallel lines on same tower was established for theoretical analysis. Electromagnetic transient model was also established in EMTDC/PSCAD. Both theoretical analysis and simulation result pointed that: the inappropriate overhead line arrangement of tower induces the unbalance phase current. The mechanism of unbalance phase current was revealed and optimal arrangement of parallel transmission line on same tower was given.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - M. Tang AU - C. Zhang AU - M. Li AU - L.J. Ding AU - H. Zhang AU - W. Wei AU - F. Tang PY - 2015/10 DA - 2015/10 TI - Research on Unbalance Phase Current of 500kV AC Transmission Line in Yibin UHV Converter Station BT - Proceedings of the 4th International Conference on Information Technology and Management Innovation PB - Atlantis Press SP - 188 EP - 193 SN - 2352-538X UR - https://doi.org/10.2991/icitmi-15.2015.34 DO - 10.2991/icitmi-15.2015.34 ID - Tang2015/10 ER -