Reason Analysis for the increase of single-phase short circuit current and its suppressing measure
- DOI
- 10.2991/icitmi-15.2015.31How to use a DOI?
- Keywords
- Single-phase short circuit current; Neutral grounding; Small reactance; Autotransformer
- Abstract
Aiming at the issue that the single-phase short circuit current at the 220 kV bus of Chengdu 500kV substation exceeds the three-phase short current or even exceeds the breaking capacity of breaker, the reason is analyzed and the measure that main transformer neutral grounding by small reactance is put forward to reduce the single-phase short circuit. According to the planning power network of Sichuan, this paper analyzes the limiting effects of 500 kV autotransformer neutral grounding by small reactance on 220 kV single-phase short circuit current by simulation and calculation. This paper also analyzes the influence of neutral grounding by small reactance on insulation level of neutral point, and put forward a directive idea about small reactor's selection
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Y. Li AU - H. Zhang AU - G. Chen PY - 2015/10 DA - 2015/10 TI - Reason Analysis for the increase of single-phase short circuit current and its suppressing measure BT - Proceedings of the 4th International Conference on Information Technology and Management Innovation PB - Atlantis Press SP - 169 EP - 173 SN - 2352-538X UR - https://doi.org/10.2991/icitmi-15.2015.31 DO - 10.2991/icitmi-15.2015.31 ID - Li2015/10 ER -