DC Bias Magnetic Vibration Monitoring Method and Device Based on the Amplitude of the Core Transformer
- DOI
- 10.2991/icemc-16.2016.87How to use a DOI?
- Keywords
- Transformer vibration; DC bias; Finite element method; Monitoring device
- Abstract
In order to overcome the blindness of the installation of sensors in monitoring the vibration of the transformer, in this paper, a method for monitoring the DC bias of transformer based on the amplitude of the iron core is proposed. By establishing the circuit electromagnetic field force field model, a finite element analysis is used to obtain the vibration amplitude of the DC magnetic field at each position of the transformer core, then to collect the low frequency vibration of the core during the operation of the transformer. Analysis of the data and timely warning, can improve the accuracy of the vibration signal acquisition, to avoid the DC bias due to abnormal vibration of the transformer and accident tripping and other major accidents.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Haokai Xie PY - 2016/05 DA - 2016/05 TI - DC Bias Magnetic Vibration Monitoring Method and Device Based on the Amplitude of the Core Transformer BT - Proceedings of the 2016 International Conference on Education, Management and Computer Science PB - Atlantis Press SP - 423 EP - 428 SN - 1951-6851 UR - https://doi.org/10.2991/icemc-16.2016.87 DO - 10.2991/icemc-16.2016.87 ID - Xie2016/05 ER -