Evaluation of short-circuit current breaking capacity of circuit breaker
- DOI
- 10.2991/iceep-18.2018.266How to use a DOI?
- Keywords
- Circuit breaker, short-circuit current, dc component.
- Abstract
The development of the power grid makes the X/R value in the network become more and more large, which leads to the attenuation of the short-circuit current DC component becoming more and more slow when the fault occurs. In this situation, the ability of the breaker to break the short-circuit current is reduced. In this paper, a method of calculating the DC component and its decay time constant of the short-circuit current is given. The DC component of the short-circuit current is obtained by the envelope method, and the least square algorithm is used to calculate the decay time constant. The simulation analysis of the actual breaking capacity of the circuit breaker is given in the example, which provides guidance for the safe and stable operation of the power grid.
- Copyright
- © 2018, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yongchun Su AU - Xiaoming Wang AU - Ning Zhou AU - Zhan Shu PY - 2018/09 DA - 2018/09 TI - Evaluation of short-circuit current breaking capacity of circuit breaker BT - Proceedings of the 2018 7th International Conference on Energy and Environmental Protection (ICEEP 2018) PB - Atlantis Press SP - 1496 EP - 1500 SN - 2352-5401 UR - https://doi.org/10.2991/iceep-18.2018.266 DO - 10.2991/iceep-18.2018.266 ID - Su2018/09 ER -