Study on Operation Control Strategy of Adjacent Pump Stations in Long Distance Multistage Pumping Station Control System
- DOI
- 10.2991/iceep-18.2018.66How to use a DOI?
- Keywords
- Long-distance water. time difference control. power-on program.
- Abstract
Aiming at the operation control of adjacent pump stations in the multi-stage pumping station of a small buffer pool, a transient mathematical model of pipeline flow was established by hydraulic calculation in the pipeline to calculate the start-up time difference between pumping stations at different levels. AFT impulse software was used to measure the time difference The validity of the control mode is verified. Based on this, the time difference between start-up allowable time of multi-stage pumping station with different buffer pools is calculated and analyzed, which provides a theoretical basis and data support for the joint control of long-distance multi-stage pumping stations with small buffer.
- Copyright
- © 2018, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Xuejun Xu AU - Ying Yan AU - Qingqing Ma PY - 2018/09 DA - 2018/09 TI - Study on Operation Control Strategy of Adjacent Pump Stations in Long Distance Multistage Pumping Station Control System BT - Proceedings of the 2018 7th International Conference on Energy and Environmental Protection (ICEEP 2018) PB - Atlantis Press SP - 382 EP - 387 SN - 2352-5401 UR - https://doi.org/10.2991/iceep-18.2018.66 DO - 10.2991/iceep-18.2018.66 ID - Xu2018/09 ER -