Selection and Energy Saving Analysis of Water Pumps in Center Air Conditioning
- DOI
- 10.2991/iceep-16.2016.119How to use a DOI?
- Keywords
- Water pump, central air conditioning system, measured date, variable speed regulation, energy saving
- Abstract
Analyses the measured data of water pumps in the 10 central air conditioning projects. The results show that the measured flow rate of pump is 19.3 percent higher than that of design flow rate on average, and the measured efficiency of pump is 58.8 percent higher than that of design value on average. The higher flow rate and lower efficiency result from oversized pump head. The rate head is 87.6 percent higher than required head on average in 10 projects, which results in higher actual energy consumption than that of ideal condition. Variables speed regulation of pumps or cutting-impeller control of pumps will contribute to operation on condition of design flow rate as well as sound energy saving effects.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yongzheng Fu AU - Mengyu Xu PY - 2016/11 DA - 2016/11 TI - Selection and Energy Saving Analysis of Water Pumps in Center Air Conditioning BT - Proceedings of the 2016 5th International Conference on Energy and Environmental Protection (ICEEP 2016) PB - Atlantis Press SP - 692 EP - 698 SN - 2352-5401 UR - https://doi.org/10.2991/iceep-16.2016.119 DO - 10.2991/iceep-16.2016.119 ID - Fu2016/11 ER -