Proceedings of the 2016 5th International Conference on Energy and Environmental Protection (ICEEP 2016)

Study on the harmonics overvoltage of large-scale photovoltaic power plant system based on passive network model

Authors
Chunlai Li, Jiacheng Hao, Yongqiang Zhu, Qi Tang, Luming Ge, Linan Qu
Corresponding Author
Chunlai Li
Available Online November 2016.
DOI
10.2991/iceep-16.2016.88How to use a DOI?
Keywords
Large-scale photovoltaic power station, Harmonic overvoltage, Passive network model, Electricity collection system.
Abstract

Harmonic problem is one of the main problems that restrict the development of grid connected photovoltaic (PV) power plant. In this paper, a passive network model of harmonic transmission is established with detailed consideration of the electricity collection system structure of PV power station based on the topological structure of typical large-scale grid connected PV power station. The harmonic power flow calculation is carried out by using the nodal admittance method in MATLAB. The magnification of the harmonic voltage of each node with respect to the fundamental wave voltage is concluded. The point of common coupling (PCC) is selected as the analysis object, and compared with the calculation results of the neglect of the electricity collection system, it is found that the characteristic of the harmonic voltage amplification is obviously changed. In the end, the influences of the LCL filter on the harmonic voltage amplification of the transmission network are analyzed.

Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Download article (PDF)

Volume Title
Proceedings of the 2016 5th International Conference on Energy and Environmental Protection (ICEEP 2016)
Series
Advances in Engineering Research
Publication Date
November 2016
ISBN
978-94-6252-253-4
ISSN
2352-5401
DOI
10.2991/iceep-16.2016.88How to use a DOI?
Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Cite this article

TY  - CONF
AU  - Chunlai Li
AU  - Jiacheng Hao
AU  - Yongqiang Zhu
AU  - Qi Tang
AU  - Luming Ge
AU  - Linan Qu
PY  - 2016/11
DA  - 2016/11
TI  - Study on the harmonics overvoltage of large-scale photovoltaic power plant system based on passive network model
BT  - Proceedings of the 2016 5th International Conference on Energy and Environmental Protection (ICEEP 2016)
PB  - Atlantis Press
SP  - 509
EP  - 516
SN  - 2352-5401
UR  - https://doi.org/10.2991/iceep-16.2016.88
DO  - 10.2991/iceep-16.2016.88
ID  - Li2016/11
ER  -