A Combination of STATCOM and Distribution Transformer With Passivity-based Control for Reactive Power Compensation
- DOI
- 10.2991/iceep-16.2016.58How to use a DOI?
- Keywords
- Distribution Transformer, STATCOM, Reactive Power Compensation, Passivity-Based control, Injection Damping.
- Abstract
This paper studies static synchronous compensator (STATCOM) accessed in the system via intermediate taps on transformer high voltage wingdings. For Dyn11 type transformers, the proposed circuit configuration of DT-STATCOM is analyzed, and the function of reactive power compensation is verified. Then, the Euler-Lagrangian (EL) model of a distribution transformer-static synchronous compensator (DT-STATCOM) is established. This paper also proposes an improved ip-iq current detection method. Meanwhile, the passivity-based control (PBC) law which can decouple active and reactive power is proved. By selecting proper injecting damping, we can optimize the dynamic performance and realize fast compensation of reactive power. Finally, simulation results show the effectiveness of the proposed structure with PBC in reactive power compensation.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Jinmu Lai AU - Xianggen Yin AU - Ertao Lei AU - Yu Chen PY - 2016/11 DA - 2016/11 TI - A Combination of STATCOM and Distribution Transformer With Passivity-based Control for Reactive Power Compensation BT - Proceedings of the 2016 5th International Conference on Energy and Environmental Protection (ICEEP 2016) PB - Atlantis Press SP - 336 EP - 342 SN - 2352-5401 UR - https://doi.org/10.2991/iceep-16.2016.58 DO - 10.2991/iceep-16.2016.58 ID - Lai2016/11 ER -