Study of the On-site Calibration Technology for DC Voltage Transformer Based on Synchronous Data Acquisition
Authors
Deng-Yun Li, Jian Liu, Chun-Yan Yang, Qian-Zhu Xiong, Qi Nie
Corresponding Author
Deng-Yun Li
Available Online November 2016.
- DOI
- 10.2991/iceep-16.2016.19How to use a DOI?
- Keywords
- DC voltage transformer, DC standard voltage divider, synchronous data acquisition system, on-site calibration test
- Abstract
This paper developed a DC high voltage standard device (including the DC standard voltage divider and the synchronous data acquisition system) for the on-site calibration test of DC converter station. After selecting the appropriate circuit for on-site calibration test, this paper completed the on-site test calibration of the DC voltage transformer in Fulong converter station. The result demonstrates that the DC high voltage standard device this paper developed has the ability to ñ 800kV HVDC voltage transformer on-site calibration tests.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Deng-Yun Li AU - Jian Liu AU - Chun-Yan Yang AU - Qian-Zhu Xiong AU - Qi Nie PY - 2016/11 DA - 2016/11 TI - Study of the On-site Calibration Technology for DC Voltage Transformer Based on Synchronous Data Acquisition BT - Proceedings of the 2016 5th International Conference on Energy and Environmental Protection (ICEEP 2016) PB - Atlantis Press SP - 112 EP - 117 SN - 2352-5401 UR - https://doi.org/10.2991/iceep-16.2016.19 DO - 10.2991/iceep-16.2016.19 ID - Li2016/11 ER -