Study of Overvoltage Protection and Insulation Coordination for MMC based HVDC
- DOI
- 10.2991/iccsee.2013.593How to use a DOI?
- Keywords
- Modular Multilevel Converter, Station Faults, Overvoltage, Arrester Configuration, Insulation Coordination
- Abstract
This paper focus on overvoltage protection and insulation coordination in Modular Multilevel Converter based HVDC system planning. An overvoltage protection scheme, which bases on the topology used in Transbay project by Siemens, is proposed in this paper. The scheme draws from the characteristics of MMC-HVDC systems and the research results in classic HVDC systems, by placing arresters at some key locations in the MMC-HVDC converter station. With this scheme, the overvoltage at those key points can be limited to an acceptable range and hence protect the key equipment concerned. Since all the DC lines of the project are undersea cables, no lighting overvoltage is considered and 14 faults which could happen are carefully selected to serve as the verification conditions for the insulation design. Based on the PSCAD/EMTDC simulations and the deterministic method, the specified withstand voltage levels of the critical equipment in the converter station is calculated.
- Copyright
- © 2013, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yilei Gu AU - Xiaoming Huang AU - Peng Qiu AU - Wen Hua AU - Zheren Zhang AU - Zheng Xu PY - 2013/03 DA - 2013/03 TI - Study of Overvoltage Protection and Insulation Coordination for MMC based HVDC BT - Proceedings of the 2nd International Conference on Computer Science and Electronics Engineering (ICCSEE 2013) PB - Atlantis Press SP - 2369 EP - 2372 SN - 1951-6851 UR - https://doi.org/10.2991/iccsee.2013.593 DO - 10.2991/iccsee.2013.593 ID - Gu2013/03 ER -