HVDC Islanding Testing Analysis and Control Parameter Optimization
- DOI
- 10.2991/icaees-15.2015.135How to use a DOI?
- Keywords
- islanding mode; stability characteristic; frequency stability; control parameter optimization
- Abstract
This paper researches HVDC operating characteristics and its sensitive factors of islanding system based on JinSu UHVDC in China. Several factors such as water hammer effect coefficient, parameter of governor, load model, DC frequency controller, power system operation mode and stability control measure has influence to the system stability. To optimize UHVDC control system and ancillary power source parameter, dead area match scheme of control system is proposed as well as reasonable limit step value. The analysis and scheme in this paper is verified by the actual data of JinSu UHVDC islanding testing. The operation control strategy can support precious experience for planning and operation of HVDC projects.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Jianming Wang AU - Jian Zhang AU - Yonghua Yin PY - 2015/07 DA - 2015/07 TI - HVDC Islanding Testing Analysis and Control Parameter Optimization BT - Proceedings of the 3rd International Conference on Advances in Energy and Environmental Science 2015 PB - Atlantis Press SP - 735 EP - 741 SN - 2352-5401 UR - https://doi.org/10.2991/icaees-15.2015.135 DO - 10.2991/icaees-15.2015.135 ID - Wang2015/07 ER -