- Abstract
Carried out fire load survey of exhibition building in Beijing, and obtained a lot of data. On preliminary theoretical studies results the data has been analyzed, and then determined the fire load density standard value 876.21MJ/m2, average of 382.97 MJ/m2. The data is not refused to obey the extreme value I distribution type. In the fire protection design simulation the standard value is suggested to be used.
- Copyright
- © 2012, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Jinping Wang PY - 2012/09 DA - 2012/09 TI - The characteristics and statistical parameters of the exhibition building fire load BT - Proceedings of the 2nd International Conference on Electronic & Mechanical Engineering and Information Technology (EMEIT 2012) PB - Atlantis Press SP - 814 EP - 816 SN - 1951-6851 UR - https://doi.org/10.2991/emeit.2012.174 DO - 10.2991/emeit.2012.174 ID - Wang2012/09 ER -