Study on power transmission line ampacity calculation with nonlinear AC resistance
- DOI
- 10.2991/eesed-16.2017.23How to use a DOI?
- Keywords
- Power Transmission Line; Ac Resistance; Ampacity Calculation; Parameter Estimation
- Abstract
As the rapid development of renewable energy, energy sectors have to increase the load transfer capacity of transmission line. In order to calculate the line ampacity accurately, it is necessary to establish a valid mathematical model for line AC resistance. However, the simplified AC resistance model, which is current commonly used, does not take into account the nonlinear impact of current variation. In this paper, an modified AC resistance model regarding current-carrying variation is proposed, and the parameters in the proposed model are estimated by the experiment data. Combining IEEE standard and proposed model, the ampacity of conductor LGJ-120/25 is calculated and analyzed. The calculated results indicates that the ampacity obtained by proposed model is less than ampacity obtained by simplified AC resistance model. That means the ampacity would be overestimated and the security of transmission line would be reduced when the nonlinear impact of current variation is ignored.
- Copyright
- © 2017, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Hai-Jun Xue AU - Xu-Dong Zhang PY - 2016/08 DA - 2016/08 TI - Study on power transmission line ampacity calculation with nonlinear AC resistance BT - 2nd Annual International Conference on Energy, Environmental & Sustainable Ecosystem Development (EESED 2016) PB - Atlantis Press SP - 180 EP - 185 SN - 2352-5401 UR - https://doi.org/10.2991/eesed-16.2017.23 DO - 10.2991/eesed-16.2017.23 ID - Xue2016/08 ER -