Comparison and analysis of temperature rise characteristic of cable under the tunnel and pipe
- DOI
- 10.2991/eeeis-16.2017.23How to use a DOI?
- Keywords
- Power Cable; Temperature Rise; Pipe; Tunnel; Laying Condition.
- Abstract
In order to analyze the difference between temperature rise and the current carrying capacity of cable lines in pipe and tunnel, this paper first analyzes the temperature rise under the laying condition of tunnel and pipe and the calculation method of load flow, and applied the same test current on a 220kV cable test circuit in pipe and in tunnel under laboratory conditions, by measuring the cable conductor temperature rise with thermocouple measurement technology. The applied current is the 24h steady state current and the 24h transient current, and the difference of the temperature rise of the cable is compared under the conditions of the tunnel and the pipe under the two current conditions. The temperature rise of the cable is compared with the two different ways of laying, and the influence of the steady state current and the time varying current on the temperature rise of the cable conductor is also compared.
- Copyright
- © 2017, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Hong-Lei Li AU - Zhen-Peng Zhang AU - Shao-Xin Meng AU - Song-Hua Liu AU - Shu-Lian Xie PY - 2016/12 DA - 2016/12 TI - Comparison and analysis of temperature rise characteristic of cable under the tunnel and pipe BT - Proceedings of the 2nd Annual International Conference on Electronics, Electrical Engineering and Information Science (EEEIS 2016) PB - Atlantis Press SP - 168 EP - 174 SN - 2352-5401 UR - https://doi.org/10.2991/eeeis-16.2017.23 DO - 10.2991/eeeis-16.2017.23 ID - Li2016/12 ER -