Proceedings of the Conference on Broad Exposure to Science and Technology 2021 (BEST 2021)

1 X 1000 Kva Transformator Measurement Analysis Using Vector Group Dyn-11 and Off Load Tap Changer

Authors
Setiyo Budiyanto1, *, Imelda Uli Vistalina Simanjuntak1, Lukman Medriavin Silalahi1, Agus Dendi Rochendi2, Freddy Artadima Silaban1
1Department of Electrical Engineering Universitas Mercu Buana, Jl. Raya Meruya Selatan, Kembangan, Jakarta 11650
2Department of Oceanographic Physics Lembaga Ilmu Pengetahuan Indonesia, Jl. Pasir Putih I, Ancol Timur, Jakarta 14430
*Corresponding author. Email: sbudiyanto@mercubuana.ac.id
Corresponding Author
Setiyo Budiyanto
Available Online 1 February 2022.
DOI
10.2991/aer.k.220131.026How to use a DOI?
Keywords
Transformer; Vector Group; Load Tap Changer
Abstract

The problem of this research is to generate electrical energy in the power plant which is located far from the load center, so it requires a transmission line in order to be distributed to the public. The purpose of this research is to find out the ratio on the primary (20,000Volt) and secondary (400Volt) power transformers using off load tap changer, then observe, operate, and analyze the comparison of calculation results with the Transformer Turn Ratio (TTR) tool. The proposed method is an analysis of the condition of the transformer in a state of extinguishing to find out the condition of the transformer’s entangler. The comparison results that have been done can be known at a voltage of 40VAC, obtained the results of testing the TTR measuring instrument when it exceeds the tolerance limit of 0.5% then the measurement results on one of the coils undergo a change in ratio. Suggestions that transformers are routinely checked, because if ignored potentially unbalance voltage on one of the coils and it will result in loss of voltage.

Copyright
© 2022 The Authors. Published by Atlantis Press International B.V.
Open Access
This is an open access article under the CC BY-NC license.

Download article (PDF)

Volume Title
Proceedings of the Conference on Broad Exposure to Science and Technology 2021 (BEST 2021)
Series
Advances in Engineering Research
Publication Date
1 February 2022
ISBN
978-94-6239-526-8
ISSN
2352-5401
DOI
10.2991/aer.k.220131.026How to use a DOI?
Copyright
© 2022 The Authors. Published by Atlantis Press International B.V.
Open Access
This is an open access article under the CC BY-NC license.

Cite this article

TY  - CONF
AU  - Setiyo Budiyanto
AU  - Imelda Uli Vistalina Simanjuntak
AU  - Lukman Medriavin Silalahi
AU  - Agus Dendi Rochendi
AU  - Freddy Artadima Silaban
PY  - 2022
DA  - 2022/02/01
TI  - 1 X 1000 Kva Transformator Measurement Analysis Using Vector Group Dyn-11 and Off Load Tap Changer
BT  - Proceedings of the Conference on Broad Exposure to Science and Technology 2021 (BEST 2021)
PB  - Atlantis Press
SP  - 155
EP  - 159
SN  - 2352-5401
UR  - https://doi.org/10.2991/aer.k.220131.026
DO  - 10.2991/aer.k.220131.026
ID  - Budiyanto2022
ER  -