1 X 1000 Kva Transformator Measurement Analysis Using Vector Group Dyn-11 and Off Load Tap Changer
- DOI
- 10.2991/aer.k.220131.026How to use a DOI?
- Keywords
- Transformer; Vector Group; Load Tap Changer
- Abstract
The problem of this research is to generate electrical energy in the power plant which is located far from the load center, so it requires a transmission line in order to be distributed to the public. The purpose of this research is to find out the ratio on the primary (20,000Volt) and secondary (400Volt) power transformers using off load tap changer, then observe, operate, and analyze the comparison of calculation results with the Transformer Turn Ratio (TTR) tool. The proposed method is an analysis of the condition of the transformer in a state of extinguishing to find out the condition of the transformer’s entangler. The comparison results that have been done can be known at a voltage of 40VAC, obtained the results of testing the TTR measuring instrument when it exceeds the tolerance limit of 0.5% then the measurement results on one of the coils undergo a change in ratio. Suggestions that transformers are routinely checked, because if ignored potentially unbalance voltage on one of the coils and it will result in loss of voltage.
- Copyright
- © 2022 The Authors. Published by Atlantis Press International B.V.
- Open Access
- This is an open access article under the CC BY-NC license.
Cite this article
TY - CONF AU - Setiyo Budiyanto AU - Imelda Uli Vistalina Simanjuntak AU - Lukman Medriavin Silalahi AU - Agus Dendi Rochendi AU - Freddy Artadima Silaban PY - 2022 DA - 2022/02/01 TI - 1 X 1000 Kva Transformator Measurement Analysis Using Vector Group Dyn-11 and Off Load Tap Changer BT - Proceedings of the Conference on Broad Exposure to Science and Technology 2021 (BEST 2021) PB - Atlantis Press SP - 155 EP - 159 SN - 2352-5401 UR - https://doi.org/10.2991/aer.k.220131.026 DO - 10.2991/aer.k.220131.026 ID - Budiyanto2022 ER -