Online Detecting Method for Transformer Winding Deformation Based on Current Extraction
- DOI
- 10.2991/amcce-15.2015.347How to use a DOI?
- Keywords
- Transformer winding deformation; Online detection; Higher harmonic; FRA
- Abstract
Transformer winding deformation is common in transformer faults. Offline monitoring is mostly used in diagnosis of winding deformation, which has some limitations. So an online detecting method based on extraction of current is proposed. The method increases the higher harmonic of the current that flows into the input end of transformer appropriately. This higher harmonic is regarded as sweep frequency source. Current flowing into the input and outlet end of transformer is measured. And high frequency components are extracted to structure response curves. Transformer winding deformation is diagnosed through the analysis of response curves. The simulation results showed that winding deformation can be reflected effectively in this method.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Ning Zhang AU - Meng Zhang AU - Yuan-yuan Zhang AU - Yong-li Zhu PY - 2015/04 DA - 2015/04 TI - Online Detecting Method for Transformer Winding Deformation Based on Current Extraction BT - Proceedings of the 2015 International Conference on Automation, Mechanical Control and Computational Engineering PB - Atlantis Press SN - 1951-6851 UR - https://doi.org/10.2991/amcce-15.2015.347 DO - 10.2991/amcce-15.2015.347 ID - Zhang2015/04 ER -