Analysis And Modification Of Scaling Differentiation Of Spray Towers In Tianshengqiao Converter Station
- DOI
- 10.2991/aeecs-16.2016.57How to use a DOI?
- Keywords
- converter valve; spray tower; scaling; valve cooling system.
- Abstract
When disassembling and checking the outer cold water pipeline of the third cooling tower in Tianshengqiao Station, we found that the scaling circumstances of the outer cold water pipeline inwall of the 1# tower, 2# tower and 3# tower are very different from that of the radiating coiler. In the 3 cooling towers, the scaling circumstances of 3# tower and 1# tower are the most serious and least serious respectively. Hereby, we designed three groups of experiments by selecting the flow of inside circulating water, the flow of spray water and the water resistance in the pipeline as the variables according to the influencing factors of scaling, and then respectively conducted research on the effects of the 3 factors on scaling, and lastly we put forward an improvement scheme for the valve cooling system of Tianshengqiao Station by combining the research conclusions and practical situation.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Shuyong Guo AU - Feng Zheng AU - Xueyan Shi PY - 2016/05 DA - 2016/05 TI - Analysis And Modification Of Scaling Differentiation Of Spray Towers In Tianshengqiao Converter Station BT - Proceedings of the 2016 International Conference on Advances in Energy, Environment and Chemical Science PB - Atlantis Press SP - 299 EP - 304 SN - 2352-5401 UR - https://doi.org/10.2991/aeecs-16.2016.57 DO - 10.2991/aeecs-16.2016.57 ID - Guo2016/05 ER -